Telescope Dome Ventilation
The 0.9-m at sunset with 7 of the 11 ventilation louvers visible.
In August 1994, dome vents were added to the 0.9-m dome
to provide much improved flow-through ventilation as part of an image
quality improvement project. The 11 individually controllable vents are
located opposite the dome slit to allow the dome air to flush several
times per minute under typical wind conditions. Rapid flushing helps
eliminate warm air pockets from forming in the dome, which in turn,
reduces convection that would otherwise compromise image quality (that
is, "seeing").
Normally, some complement of vents will be opened at the beginning of the night,
around sunset, and closed when the telescope is closed. Under typical
observing conditions, this is done in the "automatic" mode described
below. If the dome is iced up, the vents may need to be broken free.
Based on limited testing, the dome flushes
adequately with about half the vents open during mild wind conditions.
The current default configuration is for vents 2,3,4,9,10,11 to be
open.
Under the following conditions the observer should restrict the air
flow by closing some or all of the vents.
- High gusting winds that cause the telescope to bounce.
- The dome shutter is opened during the day and the outside temperature
is higher than inside.
Selective operation of the vents is done by setting the switches on the
control panel located near vent #7, opposite the dome shutter, as
described in the "detailed operation" section below.
If the air is very calm, less than about 5 mph, you may wish to open
additional vents.
Automatic Operation of the Vents
The 6 default vents will open (or close) automatically when the dome shutter is
opened (or closed) if the control panel switch is set to "Automatic".
This is the usual mode of operation and will be ideal most of the time.
The 6 desired toggle switches in the "Together-Off-Separate" switch row must be
set to "Together".
Disabling Operation of the Vents
There may be times when the extra air flow is undesirable.
If you want the vents to remain closed when the shutter is open, the control
panel main switch ("Auto-Off-Manual") should be set to "Off".
Detailed Manual Operation of the Vents
In this mode, one can open or close any or all of the 11 vents individually.
The vent control panel consists of four types of switches as described
below. The term "ensemble of vents" refers to those vents whose
"Together-Off-Separate" switches are set to "Together".
- Auto-Off-Manual - this is the main control switch at the top
of the control box.
- Auto - Enables automatic open/close of the ensemble of vents when the
dome shutter is opened/closed. This disables manual open/close operations
from the "Open-Close" main switch (see next major bullet).
- Off - Disables both automatic and manual open/close operation of the
ensemble of vents.
- Manual - Disables automatic open/close of the ensemble of vents when
the dome shutter is opened/closed. Enables manual open/close of the
ensemble of vents with the "Open-Close" main switch.
- Open-Close - This switch operates on the ensemble of vents.
It is a "momentary" switch which must be held
while the vents continue to open or close.
- Together-Off-Separate - This is a row of 11 switches, each having
3 positions, to control the detailed operation of an individual vent.
- Together - Include this vent as part of the ensemble.
- Off - Remove this vent from the ensemble and disable it from manual
open/close operations.
- Separate - Remove this vent from the ensemble and enable it to be
opened/closed manually by its individual open/close manual switch (see next
major bullet).
- Open-Close (row of 11) - If the individual vents
"Together-Off-Separate" switch is set to Separate, then it can be
opened/closed by its individual open/close switch from this row
(towards the bottom of the control panel).